Power metre siemens SICAM P power quality analyzer current voltage power factor measurement
$129

Overview

SICAM P35 and SICAM P36 3-phase electronic multi-function power meters integrate measurement, power
metering, remote communication and control, large screen LCD and communication functions. It is designed
for measuring power grid parameters such as voltage, current, power, power factor and frequency and metering
active and reactive power. RS485 communication support MODBUS-RTU communication protocol. Binary
input and output functions are optional.
This product is extensively applicable to power substation and distribution automation system, industrial control
and industrial automation system, energy management system and community power monitoring, etc.
This 3-phase electronic multi-function power meter meets following standards:
• IEC 62052-11:2003 (Electricity metering equipment (a.c.) General requirements, tests and test conditionsPart 11: Metering
equipment) standard
• IEC 62053-22:2003 static meters for active energy (classes 0.2 S and 0.5 S)
• IEC 62053-23:2003 static meters for reactive energy (classes 2 and 3)
• Modbus-RTU

Features:

This project uses high-precision sampling and metering unit and high-speed MCU data processing unit, supporting high-precision,wide-range and accurate measurement and quick data analysis; segmented multi-line WVA LCD, realizing various and abundant display; white backlight for LCD, satisfying the need for viewing data in dark environment; NVRAM, supporting long-time data storage without data loss even in the event of power failure; RS485 communication port and industrial standard communication protocols, realizing flexible and reliable communication.

Specification

ltem

Technical Data

Product standard

EC61557-12:2007

Input comnecion

3-phase 3 wire.3-phase 4-wire. sinle phase

Measurement

voltage

Reference voltage Un: AC380 V, AC220 V, AC100 V,
AC57.7V
Measuring range: 10 V ... 276 V phase voltage
Maximum measuring range: 400 V phase voltage
Power consumption: < 0.1 VA (single phase @220VAC)
Accuracy: RMS 0.2%
Resolution: 0.01 V

Current

Rated current l.: 1 A, 5 A
Measuring range: 0.015 A ... 6 A
Maximum measuring range: 9 A
Power consumption: < 0.3 VA (single phase @5A)
Accuracy: RMS 0.2%
Resolution: 0.001 A

Power (active, racdive,)

Accuracy: 0.5%
Resolution: 0.001 kW/kVar/kVA

Power gid frequency

Measuring range: 45Hz._ 65Hz
Accuracy: 0.2%
Resolution: 0.01 Hz

Meteting

Active power

Accuracy leve: 0.5 s, Acc:IEC 62053-22
Resolution: 0.01 kWh, 5000 imp/kWh

Reactive power

Accuracy: Class 2, Acc. To IEC 62053-23
Resolution: 0.01 kvarh, 5000 imp/kvarh

Diglta signgal

Power pulse output

2 electic energy (active and reactive) pulse outputs Opto-coupler isolation.4.000 Vrms

Binary output (pponanl

2 electromagnetic relay output
Normal Open Contact
Contact capacity: AC 250 V /3 A, DC 30 V /3 A

Binary Input (optional)

4 dry conmact imputs
Opto-coupler isolation, 4,000 VRMS

Communication

RS-485 port

Interface type: Twisted Pair, Half Duplex Transmission
Communication rate: 600 bps ... 38,400 bps
Protocol: Modbus-RTU

Environment

Operating temp.

-25℃...+60℃

operating temp. limt

-35℃...+70℃

Relative humidity

≤95%(condensation free)

  Tel

  18694970015

  Email

  18694970015@163.com

     WeChat 

   

WeChat QR code
Nanjing Zhuneng Electric Co., Ltd

Mobile number: 18694970015

WeChat: power1411913

Email: 18694970015@163.com

Address: Building 16, Liandong U Valley Industrial Park, No.24 XuefuRoad, Jiangbei New District, Nanjing, Jiangsu, China