I. Pre-experimental Preparations
(1) Entry of Set Values and Parameters (Device + Tester)
Phase sequence sensitivity angle: 80°
Grounding distance setpoint
Section I: 4 Ω; Section II: 6 Ω, time limit 0.5s; Section III: 8 Ω, time limit 1s
Interphase distance setpoint
Section I: 4 Ω; Section II: 6 Ω, time limit 0.5s; Section III: 8 Ω, time limit 1s
Protect Control Word Settings
Distance to Sections I/II/III: Implemented
(2) Tester Test Mode
Select the short-circuit calculation interface and employ a state sequence test:
·State 1: Normal state; three-phase positive sequence full voltage, three-phase no current; maintained for 2s
·State 2: Fault state; apply a fault impedance and maintain the fault duration according to the test settings.
Test criteria:
1.0.95× fixed value: at a sensitivity angle of 80°, the protection should operate reliably; at an impedance angle of 260° (non-sensitive zone), the protection should remain inactive
2.1.05× fixed value: When the sensitivity angle is 80°, the protection remains reliably inactive (boundary verification)
II. Project-by-Project Testing Procedures
Project 1: Distance to Section I calibration (ZZD = 4 Ω)
Test 1.1: 1.05×ZZD, impedance angle 80°, fault duration 0.1s
1.State 1: Normal state; maintain for 2s
2.State 2: Fault impedance = 1.05×4 = 4.2 Ω, impedance angle = 80°, maintained for 0.1s
3.Expected Outcome
Test 1.2: 0.95×ZZD, impedance angle 80°, fault holding time 0.1s
1.State 1: Normal state; maintain for 2s
2.State 2: Fault impedance = 0.95 × 4 = 3.8 Ω; impedance angle = 80°; maintain for 0.1s
3.Expected Outcome
Test 1.3: 0.95×ZZD, impedance angle 260°, fault holding time 0.1s
1.State 1: Normal state; maintain for 2s
2.State 2: Fault impedance 3.8 Ω, impedance angle 260°, maintained for 0.1s
3.Expected Outcome
Test 1.4: 0.7×ZZD, impedance angle 80°
1.State 1: Normal state; maintain for 2s
2.Condition 2: Fault impedance = 0.7×4 = 2.8 Ω; impedance angle = 80°
3.Expected Outcome
Project 2: Distance for Section II calibration (ZZD = 6 Ω, time limit = 0.5 s)
Test 2.1: 1.05×ZZD, impedance angle 80°, fault holding time 0.6s
1.State 1: Normal state; maintain for 2s
2.Condition 2: Fault impedance = 1.05×6 = 6.3 Ω, impedance angle = 80°, maintained for 0.6s (greater than the setting value of Section II, 0.5 s)
3.Expected Outcome
Test 2.2: 0.95×ZZD, impedance angle 80°, fault holding time 0.6s
1.State 1: Normal state; maintain for 2s
2.State 2: Fault impedance = 0.95×6 = 5.7 Ω, impedance angle = 80°, maintained for 0.6s
3.Expected Outcome
Test 2.3: 0.95×ZZD, impedance angle 260°, fault holding time 0.6s
1.State 1: Normal state; maintain for 2s
2.State 2: Fault impedance 5.7 Ω, impedance angle 260°, maintained for 0.6s
3.Expected Outcome
Project 3: Distance verification for Section III (ZZD = 8 Ω, time limit = 1 s)
Test 3.1: 1.05×ZZD, impedance angle 80°, fault duration 1.1s
1.State 1: Normal state; maintain for 2s
2.State 2: Fault impedance = 1.05×8 = 8.4 Ω, impedance angle = 80°, maintained for 1.1s (greater than the time limit for Section Ⅲ, which is 1 s)
3.Expected Outcome
Test 3.2: 0.95×ZZD, impedance angle 80°, fault duration 1.1s
1.State 1: Normal state; maintain for 2s
2.State 2: Fault impedance = 0.95×8 = 7.6 Ω, impedance angle = 80°, maintained for 1.1s
3.Expected Outcome
Test 3.3: 0.95×ZZD, impedance angle 260°, fault holding time 1.1s
1.State 1: Normal state; maintain for 2s
2.Condition 2: Fault impedance 7.6 Ω, impedance angle 260°, maintained for 1.1s
3.Expected Outcome
III. Test Records and Key Criteria for Assessment
Each test record: fault impedance, impedance angle, fault holding time, device operation message, trip type (single trip / three-phase trip / permanent trip); for ground faults (single-phase ground faults on AN/BN/CN): distance protection triggers a single trip; for phase-to-phase faults (short circuits between phases AB/BC/CA): distance protection triggers a three-phase trip; the trip output for Section III is a permanent trip at 260°, which represents the angular position outside the impedance circle and is used to verify the direction and sensitivity-angle blocking; at this angle, even if the impedance magnitude is below the set value, the protection should not operate; time margin: verify that the fault holding time for Section II> 0.5s and for Section III> 1s, thereby ensuring sufficient time allowance for the protection and validating the delay logic.
IV. Trial Completion
1.Upon completion of the test, clear the tester's output and restore the device's pressure plate and control word to the operating state.
Organize the test reports and verify whether each action and behavior, as well as the timing of each action, conforms to expecta