186-9497-0015
PSM691U

Measurement and Control Device PS0U series of protection by the line protection, transformer protection, capacitor protection, reactor protection, standby power from the cast, composed of motor protection, can be used for 110kV and below voltage levels of various industrial and mining enterprises and power industry. By using a high-performance 32-bit CPU to integrate protection, measurement and control, and communication functions, it is suitable for substation integrated automatic systems or new energy power plant electrical automation systems. Devices can be installed Group centralized screen can also be directly installed in the switch cabinet to carry out decentralized control.

Technical Features

²Using the most popular high-speed processor, frequency up to 200 MHz, rich built-in resources, easy external circuit design, product manufacturing quality assurance and stability. Sufficient hardware resources, 8M bytes Flash Memory.

²Measuring three-phase current and zero-sequence current (Ia, Ib, Ic, I0), three-phase or line voltage (Uan, Ubn, Ucn, Uab, Ubc, Uca), active power P, reactive power Q, power factor cosφ, frequency f, meritorious electricity kWh, reactive power kVarh.

²The measured values of current, voltage, power, and electrical degrees not only reflect the fundamental wave, but also correctly reflect the 2~13th harmonic, and the frequency is 45~60HZ adaptive, so that the measurement results are consistent with the special measuring meter. 

²Along with DC 4 ~ 20mA analog output (can be customized for the current, voltage or power) to replace capture transmitter communicate.

²Up to 15-channel DI, users can customize the name.

²Way to protect the export of components through the tripping matrix setting, the convenience of users to select the relay action. Contact may choose to export all the relays for tripping contact (automatic return) or signal contact (after reversion back).

²Independent operating circuit which can adapt to the 0.5A~5A switch tripping and closing current, and the operating circuit is universal for AC and DC.

²GPS time synchronization can adopt the network time synchronization method, and also supports the B code time synchronization method (RS485 interface) and the SNTP method.

²Differential protection to prevent Device to start or outside the failure resulting in differential protection saturated TA maloperation criterion.

²Valid and reliable criterion disconnected TV effectively prevent low-voltage electrical components malfunction.

²Two 100M Ethernet communication interface, one RS485 communication interface, support the IEC61850, IEC60870-5-103, Modbus and other protocols.

²16 recorders, the largest recorded wave volume contains the 13-channel analog (interval 1mS). Wave was recorded using standard Comtrade format.

²The full graphical programming technology, as well as stable and reliable protection relay library, improve reliability and correctness of the procedure.

²Machine static low power consumption (about 6W), LCD module using the new technology, life expectancy increased substantially.

²High anti-interference performance, by 10 Electromagnetic Compatibility Testing & Certification, fast transients, electrostatic discharge, surge anti-interference performance are the highest grade (Ⅳ grade) standard.

²Working ambient temperature range: -25 ℃ ~ +55 ℃ (liquid crystal non-fuzzy, slow phenomenon).

Protection device type and configuration

Device Type

Function Deployment

Scope

PSL691U

LineProtectionAndControl Device

3-zone composite voltage overcurrentprotection / 3-zone directional zero-sequenceovercurrent protection / Overload protection /Autoreclosing / Manual closing synchro-check / Closing Post-acceleration protection / Lowfrequency load shedding/Undervoltage loadshedding / Lower current ground wire selection/Measurement

35kV and below theline voltage

PST691U

Transformer Differential

Protection Device

Differential Protection / Differentialinstantaneous protection / Differential currentovercurrent alarm / TA wire break blocking

Differential Protection / Differentialinstantaneous protection / Differential currentovercurrent alarm / TA wire break blocking

PST691UF

Transformer’sNoumenonProtectionDevice

Transformer’s noumenon protection /Independent Trip circuit

PST692U

TransformerBackup

Protection Device

3-zone composite voltage overcurrentprotection / Zero-sequence overcurrentprotection / Gap

zero-sequence overcurrentprotection /

Zero-sequence overvoltageprotection / Overload

protection/Startingventilation / On-load

voltage-regulatedblocking/ Measurement

PST693U

TransformerProtection

And Control Device

3-zone composite voltage overcurrentprotection / Overcurrent inverse time-limitprotection /2-zone negative sequenceovercurrent protection / HV sidezero-sequenceovercurrent protection / LV side zero-sequenceovercurrent protection / LV side zero-sequenceinversetime-limit overcurrent protection /Overloadprotection / Overvoltage protection /Undervoltage protection / Noumenon protection/ FC blocking / 4-20mA output / Measurement

Plant transformers, used transformers and ground transformers below 2000kVA

PSC691U

Capacitor Protection And

Control Device

Instantaneous overcurrent protection /Overcurrent protection / Overvoltage protection/ Undervoltage protection /Zero-sequenceovercurrent protection /

Neutral unbalanceovercurrent protection /

Neutral unbalanceovervoltage protection /

Measurement

Shunt CapacitorBank

PS691U

ReactorDifferential

ProtectionAnd Control Device

Differential Protection / Differentialinstantaneous protection / 3-zone compositevoltage overcurrent protection /Zero-sequenceovercurrent protection /

Overload protection /Measurement

Series reactor, cablelines

PSP691U

Standby Power SupplyAutomatic Throw-over

Device

Bus coupler Automatic Throw-over / Incomingline Automatic Throw-over / TransformerAutomatic Throw-over / Plant power supplyAutomatic Throw-over

Standby Power Supply Automatic Throw-over

Device

PSV691U

TV Protection Device

2-zone undervoltage protection / Busbar

insulation Check / Measurement

35kV and below TV

cabinets

PSV692U

TV parallel Device

TV parallel

Single busbarsection system

PSV693U

TV parallel Device

TV parallel / 2-zone undervoltage protection

Single busbarsection system

PSM691U

Motor Differential And

Integrated Protection

Differential protection + Integrated protection +Measurement

Asynchronous motors of 2000kW and above

PSM692U

Integrated Motor Protection And ControlDevice

Instantaneous overcurrent protection /Overcurrent protection / 2-zonenegative-sequence overcurrent protection /Negative-sequence inverse time-limit

overcurrent / Overheat protection /Rotor-locked protection / Single-phase groundfault protection / Undervoltage protection /Overload protection / Non-electric quantityprotection / FC blocking / 4-20mA /Measurement

Asynchronous motors below 2000kW

PSM693U

SynchronousMotor Differential And Integrated Protection

Differential Protection + Integrated Protection + Measurement

SynchronousMotor

PSM694U

SynchronousMotor And Integrated Protection

Out of step protection/ Reverse power protection/ Current instantaneous protection/ Definite time-limit overcurrent protection/ Inverse time-limit negative-sequence protection/ Overheat protection/ Locked-rotor protection/ Single-phase ground protection/ Undervoltage protection/ Overload protection/ Non-electric quantity protection/ Measurement

SynchronousMotor

PSM695U

Motor Differential Protection Device

Differential protection/ Differential instantaneous protection/ Differential current overcurrent alarm/ TA wire break blocking

Asynchronous or SynchronousMotor

PSJ691U

Frequency and Voltage Emergent Device

Under-frequency load shedding / Over-frequency load shedding / Under-voltage load shedding / Over-voltage load shedding / Zero-sequence overvoltage protection

Power plant grid-connected system

PSJ692U

Anti-islanding Protection Device

Under-frequency load shedding / Over-frequency load shedding / Under-voltage load shedding / Over-voltage load shedding / Reverse power protection / Power loss protection / Zero-sequence overvoltage protection/ External intertrip

Photovoltaic wind power grid-connected system

2 Technical performance and indicators

2.1 Rated electric parameters

²Power supply

Operating Voltage:AC/DC 86~264V

Ripple coefficient:not larger than 5%

²Rated current, voltage

AC current:                               5A or 1A; (Specify when ordering)

AC Voltage:                             100V or 100V.

2.2 Principal technical indices

²Accurate operating range

Current:0.04In ~ 20In (In =5A or In =1A);

Voltage:1V ~ 150V;

Frequency:45Hz~60Hz

²Measuring accuracy

Voltage, Current:Class 0.2; (Including harmonics)

Power:Class 0.5; (Including harmonics)

Frequency:≤±0.01Hz;

4-20mA DC:Class 0.5. (Specify When Ordering)

²Setting error

Current components: ≤±2.5% setting value or ±0.01IN;

Voltage components: ≤±2.5% setting value or ±0.005UN;

Action time error: definite time protection, no more than (±1% setting value + 40)ms; inverse time limit protection, no more than ±5% setting value or ±40ms.

²Telesignalling resolution

Less than 2ms。

²GPS time-check

IRIG-B: DC Time Code, RS485 interface; NTP time-check: Ethernet interface.

²Contact capacity

Operation of circuit tripping current and closing current: 0.5A ~ 5A adaptive;AC/DC trip circuit self-adaptation.

Trip space contact: 5A (DC220V closure of capacity); signal space contact: 5A (DC220V closing capacity).

2.3 Environmental conditions

Ambient temperature:-25°C ~ +55°C

Relative humidity:5% ~95% (No condensation or freezing inside the product)

Atmospheric pressure:66Kpa ~ 106Kpa

2.4 Power consumption

AC current circuit:As IN = 5A, not larger than 0.5VA each phase;

As IN = 1A, not larger than 0.3VA each phase;

AC voltage circuit:At rated voltage, not larger 0.5VA each phase;

DC power supply circuit:For normal operation, not larger than 10W;

As the system operates, not larger than 20W.

2.5 Overload capability

AC current circuit: at 2 multiples of rated current, continuous operation; at 10 multiples of rated current, 10s is permitted; at 40 multiples of rated current, 1s is permitted.

AC voltage circuit: at 1.4 multiples of voltage, continuous operation 

2.6 Insulation performance

²Insulation resistance

Under normal test atmospheric conditions, the insulation resistance of the system between the externally leading active circuits and the open non-active metal parts as well as the housings and between the electrically unconnected circuits is measured by a 500V megger to be not lower than 100MΩ.

²Media strength

Under normal test atmospheric conditions, the system can tolerate the 50Hz, 1min. power frequency withstand voltage test and no breakthrough flashover and element damages will occur. During the test, as the voltage apply at any tested circuit, the other circuits will interconnect and ground equipotentially.

²Impulse voltage

Under normal test atmospheric conditions, such circuits as DC input circuit, AC input circuit, output contacts, etc. to ground and between the electrically unconnected circuits can tolerate the short-duration impulse voltage test of 1.2/50μs standard lightning waves and its open-circuit test voltage is 5kV.

2.7 Humid-heat tolerant performance

The system can tolerate the constant humid-heat test stipulated in GB/T7261.20. The test temperature is +40°C ±2°C, relative humidity, (93±3)% and test duration, 48h. Within 2h before the end of the test, the insulation resistance between the external lead live circuit part and the exposed non-live metal part and the shell, as well as the circuit without electrical connection should not be less than 1.5Mω; The dielectric strength shall not be less than 75% of the specified dielectric strength test voltage value.

2.8 EMC

Item

Request

1

RF radiatedelectromagnetic fieldimmunity

The protection conforms to radiated, RF electromagnetic fieldimmunity test class III stipulated in the standard GB/T 14598.9-2002(IEC 60255-22-3:2000,IDT).

2

Electric fast transientpulse group immunity

The protection conforms to electrical fast transient/burst immunity testclass Ⅳstipulated in the standard GB/T 14598.10-2007(idt IEC60255-22-4:2002).

3

1MHz pulse groupimmunity

The protection conforms to 1MHz pulse group immunity test class IIIstipulated in the standard GB/T 14598.13-2008(eqv IEC60255-22-1:2007).

4

Electrostatic dischargeanti-interference

The protection conforms to the electrostatic discharge immunity testclass 4 stipulated in the standard GB/T 14598.14-1998(idt IEC60255-22-2:1996).

5

Radiated emission valuelimiting test

The protection conforms to radiated emission value limiting test classA stipulated in the standard GB/T 14598.16-2002(IEC60255-25:2000,IDT).

6

Surge (impulse) immunity

The protection conforms to surge (impulse) immunity test class 4stipulated in the standard GB/T 17626.5-2008(idt IEC 61000-4-5:2006).

7

RF induction conduction degree harassment

The protection conforms to immunity to conducted disturbances, induced by radio-frequency fields class 3 stipulated in the standard GB/T 17626.6-2008(idt IEC 61000-4-6:2006).

8

Power frequency magnetic field immunity

The protection conforms to power frequency magnetic field immunity test class 4 stipulated in the standard GB/T 17626.8-2006(idt IEC 61000-4-8:2001).

9

Pulsed magnetic field immunity

The protection conforms to pulse magnetic field immunity test class 4 stipulated in the standard GB/T 17626.9-1998(idt IEC 61000-4-9:1993).

10

DC power supply voltage dips and voltage interruptions influence

Allow GB/T8367-1987 (eqv IEC 60255-11:1979) called for 100ms voltage interruption, 30% voltage dips 0.5s

2.9 Mechanical performance

Item

Request

1

Vibration

The system can tolerate the vibration response test of severity Class I stipulated in 3.2.1 of GB/T 11287-2000.

The system can tolerate the vibration endurance test of severity Class I stipulated in 3.2.2 of GB/T 11287-2000.

2

Impulse

The system can tolerate the impulse response test of severity Class I stipulated in 4.2.1 of GB/T 14537-1993.

The system can tolerate the impulse endurance test of severity Class I stipulated in 4.2.2 of GB/T14537-1993.

3

Collision

The system can tolerate the collision test of severity Class I stipulated in 4.3 of GB/T 14537-1993.

PSM 691U Motor Differential And Integrated Protection 

MainFunctions:



Installation dimensions



 
 
Previous : PSR691U
Next : PSL691U

  Tel

  18694970015

  Email

  18694970015@163.com

     WeChat 

   

WeChat QR code
Nanjing Zhuneng Electric Co., Ltd

Mobile number: 18694970015

WeChat: power1411913

Email: 18694970015@163.com

Address: Building 16, Liandong U Valley Industrial Park, No.24 XuefuRoad, Jiangbei New District, Nanjing, Jiangsu, China

Copyright © 2024 Guodian Nanjing Automation Co., Ltd. All rights reserved.
Contact
Navigation
WhatsApp
Cloud computing support Feedback Manage