I. Classification of Major Protection Categories
1.Line protection: distance protection, zero-sequence protection, overcurrent protection, low-frequency load shedding, automatic transfer switching, and reclosing
2.Main transformer protection: differential protection, gas protection, gap zero-sequence protection, over-excitation protection, and backup overcurrent protection
3.Busbar protection: busbar differential protection, busbar interconnection overcurrent protection, and busbar interconnection charging protection
4.Motor protection: differential, locked-rotor, overload, negative-sequence overcurrent, and low-voltage protection
5.Capacitor protection: overcurrent protection, voltage imbalance, overvoltage and undervoltage, and zero-sequence overcurrent
二、Principle of Distance Protection
Measure the voltage and current in the faulted phase, then calculate the measured impedance Z = U/I; the protection is activated when the measured impedance is lower than the set impedance. The protection is divided into Sections I, II, and III, which are coordinated hierarchically: Section I provides rapid tripping for most of the line; Section II covers the entire length of the line; and Section III serves as remote backup and can be coordinated with input signals to implement energization/de-energization and blocking logic. ✅ Operating procedure:
1.Acquire the analog voltage and current signals on this side
2.Calculate the measured impedance of the fault circuit
3.Compare the measured impedance with the setpoint impedance for this section
4.Classify input/feedback signals as open or locked, and determine whether the opening condition is met
5.When the impedance condition is satisfied and the delay time expires, the protection trip output is activated.
III. Principle of Overcurrent Protection
Based on the characteristic that the fault current increases during a fault, protection is activated when the current exceeds the protection setting. Protection modes include instantaneous overcurrent protection, time-limited instantaneous overcurrent protection, and time-limited overcurrent protection (Section III); coordinated operation between upstream and downstream levels is achieved through staged time settings, and the protection can be activated or deactivated via the input/output and pressure plate control functions. ✅ Operating procedure:
1.Phase current in the CT acquisition circuit
2.Compare the current amplitude with the set value of the corresponding current segment
3.Verify the soft pressure plate, control word, and energized/de-energized status
4.When the current continuously exceeds the set limit, the protection system begins timing.
5.Upon reaching the setting delay, the trip output
IV. Principle of Zero Sequence Protection
Single-phase ground faults generate zero-sequence voltage and zero-sequence current; zero-sequence protection operates by detecting the zero-sequence component and is specifically designed for ground faults. It is widely used in systems with non-effective neutral grounding or high-current grounding systems. ✅ Operating procedure:
1.Measure three-phase voltage and three-phase current; generate the zero-sequence signal locally, or connect it to an external zero-sequence CT.
2.Calculate the magnitudes of the zero-sequence current and zero-sequence voltage
3.Compare with the zero-sequence setting and simultaneously verify the energization/discharging logic
4.Start the timer after crossing the limit
5.Delayed arrival triggers a trip or alarm signal
V. Principle of Low-Frequency Load Shedding Protection
When the system experiences an active power deficit, the frequency decreases; low-frequency load shedding then progressively disconnects loads according to the frequency setpoint and slip setpoint, preventing a sustained collapse of the grid frequency and maintaining system stability. ✅ Operating procedure:
1.Real-time acquisition of busbar voltage, calculation of system frequency and frequency rate of change (slip)
2.Comparison with the frequency setpoints and slip setpoints for each operating cycle
3.Verify the lockout conditions (e.g., low-voltage lockout)
4.Meet the setpoint condition and confirm after a delay
5.Remove the corresponding load branch in each cycle
VI. Principle of Automatic Transfer (Standby Transfer)
When the operating power supply experiences a voltage drop and the switch trips, the device automatically switches to the backup power supply according to a preset logic, ensuring continuous power supply to the load; this can be achieved through methods such as incoming-line backup switching and busbar interconnection backup switching. ✅ Operating procedure:
1.Continuously acquire busbar voltage and switch-position input signals
2.Identify power-loss conditions such as no voltage, no current, or a change in switch position.
3.Verify the standby charging conditions and ensure there are no lockout signals
4.First, switch off the power supply and confirm that the position is correctly set.
5.Switch on the backup power supply switch to complete the power supply transfer
VII. Principle of Reclosing
After an instantaneous fault causes the circuit breaker to trip, the circuit breaker automatically re-closes after a predetermined delay, allowing power supply to be restored; a permanent fault will cause the circuit breaker to trip again. ✅ Operating procedure:
1.Collect the switch position and the protection trip input signal
2.After the protection trip occurs, charging begins once the unlocking conditions are met.
3.Charging complete; awaiting trip trigger
4.Switch off the protective switch and confirm that the switch is in the off position.
5.Upon timeout, issue a closing command
VIII. Principle of Differential Protection for the Main Transformer
Kirchhoff's current law: During normal operation and external faults, the vector sum of the currents entering and leaving the transformer is close to zero; during an internal transformer fault, the vector sum of the currents on both sides increases significantly, causing the differential protection to operate; this constitutes the primary protection for the transformer. ✅ Operating procedure:
1.Acquire CT currents on the high-voltage and low-voltage sides
2.Perform phase correction and balance-factor compensation for the currents on both sides
3.Calculate differential current and braking current
4.Comparison of differential current with starting setpoint and braking characteristic curves
5.When the operating conditions are met, instantaneous tripping occurs.
IX. Principle of Gas Protection
When an internal fault occurs in an oil-immersed transformer, the insulating oil undergoes thermal decomposition, generating gas; light gas indicates a minor fault and triggers an alarm; heavy gas indicates a severe fault and causes immediate tripping. ✅ Operating procedure:
1.The gas relay collects signals indicating oil flow and gas accumulation, and transmits these inputs to the protection device.
2.Low methane: When gas accumulation reaches the threshold, an alarm is triggered
3.Heavy gas: A fault generates a large amount of oil and gas, causing the oil flow to impact the baffle
4.Confirm that the signal is valid and that the lockout is correct
5. Heavy gas trip: open the circuit breakers on all sides of the transformer
X. Principle of Zero Sequence Protection for Gaps
For a neutral-point gap-grounded transformer, when a single-phase ground fault occurs in the system and the neutral-point voltage rises sufficiently to cause breakdown and discharge through the gap, a zero-sequence current is generated in the gap, which serves to protect the insulation of the transformer's neutral point. ✅ Operating procedure:
1.Acquire zero-sequence CT current and zero-sequence voltage during sampling intervals
2.Determination of the zero-sequence component generated by gap breakdown
3.Avoid normal unbalanced currents and compare with the set value
4.Avoid transient interference; implement time-delay discrimination
5.Once the conditions are met, switch off the transformer switch.
XI. Principle of Excitation Protection
Excessively high transformer voltage and excessively low frequency can cause magnetic flux saturation in the core, a sharp increase in the excitation current, and overheating that damages the core; over-excitation protection monitors the U/f ratio to provide protection. ✅ Operating procedure:
1.Measure busbar voltage and calculate frequency
2.Calculate the U/f ratio
3.and comparison with the overexcitation setpoint
4.Cumulative overheating effect based on the inverse time-delay characteristic
5.Reach the setpoint for the actuation, trigger an alarm, or cause a trip
XII. Motor Protection
Differential protection: Measures the currents on both sides of the motor; when an internal fault occurs, the differential current exceeds the set limit, triggering the motor's main protection. Stalling protection: If the motor fails to rotate for an extended period after startup and the current remains high, the protection trips after a time delay. Overload protection: When the long-term load exceeds the rated value, heat accumulates over time, preventing the windings from overheating and burning out. Negative-sequence overcurrent protection: In three-phase asymmetric faults or phase-loss conditions, a negative-sequence current is generated; this current damages the rotor, and the protection trips once the limit is exceeded. Low-voltage protection: When the busbar voltage is too low, the motor's torque becomes insufficient, and the motor is disconnected according to the preset time limit.
XIII. Capacitor Protection
1.Overvoltage and undervoltage protection: Monitor the terminal voltage of the capacitor; if the voltage is excessively high, it will cause component breakdown; if it is excessively low, it prevents resonance; and it triggers an action when the limit is exceeded.
2.Zero-sequence overcurrent protection: breakdown of internal components in the capacitor or single-phase grounding generates a zero-sequence current.
3.Voltage imbalance protection: Damage to internal components in a single capacitor causes an imbalance in the three-phase voltages; detection of an imbalance voltage triggers an alarm and trip.
4.Harmonic protection: When system harmonic levels exceed limits, harmonic currents in capacitors are amplified; monitor the harmonic components to protect the capacitors.