The procedure is as follows:
1. Set device off-line.A. It can be achieved by Easergy Studio:
B. By means of keys on front panel (HMI)
- Go through: Parameters > Function parameters > Global > MAIN to the parameter: [003.030] MAIN Device on-line
- Push 'ENTER'
- Enter password (default one is: 'LEFT' > 'RIGHT' > 'UP' > 'DOWN' > 'ENTER' (LED: EDIT MODE lights on)
- Change value to 'No (= off)'
- Accept with 'ENTER' key (LED: OUT OF SERVICE lights on)
2. Execute cold restart.This could be done from HMI only !
- Go through: Operation > Control and testing > MAIN > to the position [009.254] MAIN Cold restart
- Push 'ENTER'
- Enter password (default one is: 'LEFT' > 'RIGHT' > 'UP' > 'DOWN' > 'ENTER' (LED: EDIT MODE lights on)
- Change value to 'EXECUTE'
- Accept with 'ENTER' key
3. Reset alarms
A. It can be achieved by Easergy Studio:
B. By means of keys on front panel (HMI)
- Go through: Operation > Control and testing > MT_RC to the parameter: [003.008] MT_RC Reset record. USER
- Push 'ENTER'
- Enter password (default one is: 'LEFT' > 'RIGHT' > 'UP' > 'DOWN' > 'ENTER' (LED: EDIT MODE lights on)
- Change value to 'Execute'
- Accept with 'ENTER' key (LED: ALARM lights off permanently)
Warning
If ALARM LED is in ON position - please read content of the monitoring record and act accordingly. Check the Technical Manual for details.